We performed energy audits on five different multi screen movie theaters last week in Utah County, UT. These were medium size (4-8 screen) around 25,000- 40,000 square foot buildings. There was one thing in common with 4 of the 5.  No Makeup Air!!  These cinemas were using the Christie Xenon projectors that need exhaust cooling fans connected to the outside. Christie recommends 400 - 750 cfm fans for their projectors. We tested these exhaust fans to be right at 600 cfm. If you multiply 600 cfm by 6 or 8, we are talking about 4,000 cfm being pulled out of the building, mostly through the doors in the lobby. This amounts to multiple ACH (air changes per hour) and the main reason for the $600-800 monthly heating bills.

In the energy audit report we highly recommend the installation of an Acme Direct Fired Gas Heated Make Up Air Unit that would supply 4,000 cfm of heated air to make up for the conditioned air being sucked out by the projector fans.

The rooftop HVAC units were are clean and properly installed, along with the projector exhausts and concession condensers - what is absent is any source of make up air.

The larger screened MegaPlex (12-20 screen) Cinemas that we have audited all had multiple make up air units.

The ACME Heated Make Up Air Unit:

ACME heated make up air unit

Movie Theater roof top units Movie Theater roof top units

8 inch exhaust for Christie Xenon projector:

Movie Theater Energy Audit

 

Alamo Real Estate Inspections Est. 1986 | Alamo Infrared Building Inspections and Energy Audits

 

Ed Newman  |  801-651-5484  |  ed@umrt.com |  umrt.com

Utah's Largest and Oldest Infrared Real Estate Inspection and Energy Auditing Company ▫ Established in 1986

Residential ▫ Commercial ▫ Industrial ▫ Medical ▫ Government Buildings ▫ Local ▫ State ▫ Federal

 

 

3 Comments on Energy Auditing Movie Theatres - The top energy saving tip for multi screen theater operators

NOV
08
2010
405,185 Points 15 Featured Posts Localism Sponsor Outside Blog Hit Router Called Shot Master

Pretty impressed with thermal imaging. The always seems to be a new angle at working with infrared.

6:49pm • #1
328,358 Points 2 Featured Posts

After 6 years, I couldn't imagine inspecting with out it.

7:18pm • #2
NOV
09
2010
586,344 Points 4 Featured Posts Outside Blog Called Shot Master
Thanks for this great information, I will be sure to pass it on. 
6:10am • #3


What does the graphic say?
Leave a response…


(optional)
Spam Prevention:
 
D50dd Rainmaker_large

Ed Newman

Riverton, UT

More about me…

Alamo Infrared Energy Audits & Building Inspections

Address: 8315 South Main Street, Suite G, Midvale, UT, 84047

Office Phone: (801) 651-5484

Cell Phone: (801) 661-2198

Email Me

Specializing in Large Residential and Commercial and Government Buildings and Structures | Utah Energy Audit | Utah Mold and Radon Testing


Listings

Links

Archives

RSS 2.0 Feed for this blog