GFCI (Ground Fault Circuit Interrupter) protection is a system that shuts down the

protected electric circuit -- opens it -- when it senses an unexpected loss of power,

presumably to ground. GFCI protection devices constantly monitor and compare the

amount of power flowing from the panel on the hot or phase wire and the amount

returning on the neutral wire. Any time the returning power drops even slightly below the

amount being supplied, the protection device will trip and open the circuit.

A GFCI is the only protection device designed to protect people against

electric shock from an electrical system. Because of this, we need to understand what a

GFCI is, how it works, and its limitations.

The first requirement for GFCI protection appeared in the National Electrical Code

(NEC) in 1971 and became effective January 1, 1973. The requirement only included

exterior receptacles and swimming pool circuits. The rest were added over the next

twenty years. Wet bars, the latest addition, were first included in the 1993 NEC.

We need only to look to the NEC for the definition of a GFCI. The NEC defines it as "a

device intended for the protection of personnel that functions to de-energize a circuit or

portion thereof within an established period of time when a current to ground exceeds

some predetermined value that is less than that required to operate the over current

protective device of the supply circuit."

A GFCI protection device operates on the principle of monitoring the imbalance of

current between the circuit's ungrounded (hot) and grounded (neutral) conductor. It does

not monitor the grounding conductor, and so it will still operate in a circuit without a

ground. GFCI devices, including receptacles and circuit breakers, work by passing both

the hot wire and the neutral wire through a sensor - such as a differential transformer -

and connecting the sensor to a solenoid or relay that opens switch contacts built into the

power conductors inside the device.

GFCIs are designed to protect us against a ground fault, which is an unintended loss of

power to ground -- possibly through a person. The regular grounding system protects the

equipment that is attached (or plugged in) to the circuit against a ground fault in it. GFCI

devices are designed to protect people, not equipment.

In a typical 2-wire circuit, the current returning to the power supply will be equal to the

current leaving the power supply (except for some small leakage). If the difference

between the current leaving and returning through the current transformer of the GFCI

protection device exceeds 5mA (5 milliamps), the solid-state circuitry opens the

switching contacts and de-energizes the circuit. This will always happen as long as the

GFCI is in working order. However, GFCIs fail more often than most people think and

when a GFCI protection device fails, the switching contacts remain closed, and the

device continues to provide power - but no protection.

According to a study conducted by the American Society of Home Inspectors (ASHI)

published in IAEI News, November/December 1999, 21% of GFCI circuit breakers and

19% of GFCI receptacles tested did not provide GFCI protection. Yet, the circuit

remained energized! In the examined cases, failures of the GFCI sensing circuits were

mostly due to damage to the internal transient voltage surge protection that protect the

GFCI sensing circuit. This damage resulted from voltage surges from lightning and other

transients. In areas of high-lightning activity, such as Southwest Florida, the failure rate

for GFCI circuit breakers was more than 57%.

One final thought on GFCI protection: Press the test feature of the GFCI protection

device to ensure it works. These are excellent devices when properly wired. However,

never assume a GFCI protection device is operational unless you test it!

RECOMMENDATIONS FOR HOMES CONSTRUCTED PRIOR TO 1971

If you are living in a home built before the introduction of GFCI, it is recommended that

you hire a certified, licensed electrician to replace the non-GFCI receptacle outlets with

GFCI-protected types in the locations listed below. The cost of replacing existing non-

GFCI receptacle outlets is minimal compared to the safety they provide.

Receptacle outlets are required to be GFCI-protected in the following locations:

• Kitchen counter tops

• Bathrooms

• Within 6-feet of a wet bar sink

• Unfinished rooms in the basements used ONLY for storage and work area

• Garages

• All outdoor receptacle outlets

• Crawl spaces

• Rooftops

• Swimming pools

• Spas or hot tubs

 

 

 

 

0 Comments on GFCI Information


Captcha

Drag the cat to the circle on the side.

Image?id=5b3b7907eeab1bd1674907a4814bbcca6268bc17 Image?id=b4f58af216d34052755e7f9668f5f64de71cd961 Image?id=0d593d9bb6ab0e8caaa01461be82f382d54aa6e3 Image?id=d447131586ab42b2871d5eafb3cb2f5b02edb604 Image?id=533bfb0169162069f48e3e96f8a1fb5169d02be8

Accessibility option: listen to a question and answer it!

Type below the answer to what you hear. Numbers or words, lowercase:

Leave a response…


(optional)
Captcha

Drag the umbrella to the circle on the side.

Image?id=2e225554b86a2cdc3cbd36980a6d8d7ee336071c Image?id=eee3eee14dee1a44053c50d7bc53b7582af029e8 Image?id=21f19a3ae025c8ef59f04f720758d13182c5709e Image?id=2188f8587cc3a0f62dd689d2015c07bb9e0d92a5 Image?id=b2c68a130423325a37bf911b50ca5cf45330fcce

Accessibility option: listen to a question and answer it!

Type below the answer to what you hear. Numbers or words, lowercase:

 
Shane Stevens

Shane Stevens

Mansfield, TX

More about me…

Address: Mansfield, TX, 76063

Cell Phone: (000) 000-0000

Email Me



Links

Archives

RSS 2.0 Feed for this blog