I came across this the other day during a home inspection. Air Conditioning condensers have a data plate which has various information on it. One part being the maximum and minimum breaker or fuse size allowed. This particular data plate indicated the minimum size was 30-amps and the maximum size was 50-amps. So what did the builder do?

The builder put in a 50-amp breaker. No problem, right?

However, as can be seen better at the A/C disconnect box, the wires are only rated for a maximum 30-amp breaker. What happened? Maybe one contractor started the job and another finished it (improperly), thus the name of the post. Or maybe a 50-amp breaker was all that was left in the truck at the end of the day. We may never know exactly why it happened.
But what I do know is the danger of using undersized wires. The wires could basically melt, scorch or cause a fire before the breaker tripped. I advised my clients of this and explained that there were two choices:
1. Put a 30-amp breaker in the main panel. This would be within the range as indicated on the data plate. HOWEVER, when the minimum recommended breaker/fuse is used, nuisance tripping can occur. That means that when the A/C us being used during the summer, it might randomly or consistently trip off the breaker. You then have to go out to the main panel and trip it back on. Hence the name "nuisance" tripping.
2. Replace the wires with the proper rated #6 AWG copper wires and run conduit from the main panel to the A/C condenser. Conduit would have to be used since the original wires are in the wall and therefore the wall would have to be opened up to access them (not an easy task).
I hope this gives you a little more information about home inspections and their value. Be safe out there.

This happens more often than people think. I inspected a house where the contractor scratched all of the information off the nameplate. I have no idea why. I am waiting for the utilities to come on to see what happens. Thank you for the information Joseph.